Split machine from installation first, then excitation from winding. Parts come after the readings, not before.
The engine runs, so the question is what the alternator is doing
A generator that runs perfectly and produces nothing divides into three shapes, and they are not variations of the same fault. Zero voltage on all phases is an excitation problem. Reduced voltage that sags under load is usually an excitation problem too, but a different one. One phase low or absent while the others are normal is a winding or connection problem, and it behaves nothing like the first two.
The distinction matters because the first two are often fixed at the panel with a meter and a screwdriver, while the third means opening the terminal box and, in the worst case, removing the alternator. Doing the wrong one first wastes a day.
There is also a fourth shape that is not an alternator fault at all: the machine is producing correctly and the power is not reaching the load. An open main breaker, a transfer switch stuck in the wrong position, a burnt cable lug or an earth-leakage device that has tripped will all look identical from the load side. That is why the first measurement is always taken at the alternator terminals and not at the distribution board.
| What the meter shows at the alternator | Shape | Most likely area |
|---|---|---|
| Zero or a few volts on all three phases | No excitation | Residual magnetism, AVR supply, field circuit |
| Normal at no load, collapses as load is applied | Weak excitation | AVR, or a field circuit with high resistance |
| One phase low, other two normal | Winding or connection | Stator winding, terminal connection, output breaker pole |
| One phase absent, other two normal | Open circuit | Broken winding, loose lug, failed breaker pole |
| Correct at the alternator, nothing at the board | Not an alternator fault | Main breaker, ATS position, cable, earth-leakage device |
| Voltage correct but frequency wrong | Engine speed, not the alternator | Governor setting or fuel delivery |
Two safety rules that come before any measurement
The first is that a generator can produce lethal voltage from residual magnetism alone, with the engine turning and the AVR disconnected. Isolating the AVR does not make the terminals safe.
The second is that flashing a field while the machine is running, or while anyone is working on the output, is how people are killed and how alternators are destroyed. Field flashing is a stopped-machine procedure with the output isolated, and it is done once, deliberately, with the correct voltage and polarity.
Practically: stop the engine, isolate the output breaker, lock it off, prove the terminals dead with a tester that you have checked against a known live source, and only then open the terminal box. Record the readings you take, because the second visit is always more expensive than the first.
Residual magnetism: why a machine that worked in the factory produces nothing on site
A self-excited alternator needs a small magnetic field left in the rotor to begin building voltage. That residual field can be lost, and when it is lost the machine produces almost nothing however fast it turns, because there is no field for the AVR to build on.
It is lost in predictable circumstances: a long period standing idle, a machine that has been stored somewhere hot and humid, a winding that has been subjected to a short circuit or a reverse connection, or a set that was run for a short time with the output isolated and the field decaying. A set that worked at the factory and produces nothing after installation is a classic case, especially if the installation took months.
The remedy is to apply a brief direct current to the field winding with the machine stopped, in the polarity marked on the machine, at a low voltage, for a moment rather than a minute. It is a procedure to be done from the maker's instructions for that alternator, not from a general rule, because the correct terminals and the safe current differ between builds.
The AVR is the most commonly replaced part and the least often tested
The automatic voltage regulator senses output voltage and controls field current to hold it steady. When it fails, the symptom is usually either no output at all or output that swings and sags, and the part is cheap enough that many technicians replace it on suspicion rather than test it.
Testing it properly needs two things: a known-good supply to the AVR, and a field resistance that is within specification. If the field winding is open or shorted, a new AVR will fail in the same way as the old one, and the second failure is usually blamed on the supplier rather than on the winding.
There is a third possibility that costs nothing to check: the AVR supply fuse. Many builds take the AVR supply from a tap in the stator or from a permanent magnet generator, and a blown fuse in that circuit gives exactly the same dead output as a failed AVR. Check the fuse and the supply voltage at the AVR terminals before condemning the module.
Brushes, slip rings and rotating diodes
On a brushless alternator the field current reaches the rotor through a rotating rectifier fed by an exciter, and the failure points are the diodes and the exciter windings. On a brushed machine the failure points are the brushes and the slip rings, and they are visible.
Brushes wear and they wear unevenly. A brush that has worn short loses spring pressure, arcs, and leaves a burned track on the slip ring; the machine then produces voltage that fluctuates rather than voltage that disappears. Slip rings that are blackened or scored need cleaning before new brushes are fitted, otherwise the new set wears out in the same way.
Rotating diodes fail in two modes, open and shorted, and the two behave differently. An open diode reduces output and causes imbalance; a shorted diode typically collapses the field and the output with it. Both are found with a meter across each diode in both directions: a healthy diode reads one way and not the other, a shorted one reads the same both ways, and an open one reads nothing either way.
What a winding check can tell you without a megohmmeter
Continuity and balance across the three stator phases are the two checks that decide whether the machine needs to come apart. Disconnect the output links first, so the readings are of the winding alone and not of the winding plus the cables and the breaker.
The three phase resistances should be close to each other. A phase that reads open is a broken winding or a lifted connection; a phase that reads markedly lower than the others is a shorted turn, which will also run hot. Where the readings are all similar but the machine still fails under load, insulation resistance is the next check, and that needs a proper insulation tester rather than a multimeter.
Exact resistance values belong to the maker's data sheet for that alternator, not to a general guide. What this page can give you is the comparison logic: the three phases should agree with each other, the field should read as a continuous circuit, and anything that reads open or wildly different is a finding worth acting on.
One phase low or missing: the fault is not in the AVR
When two phases read normal and the third does not, excitation is working: the machine is producing a field and two of the three windings are delivering. The fault is downstream of the field, in the stator circuit or in the connection between the winding and the terminals.
The most common causes are a loose or burnt terminal lug in the alternator terminal box, a failed pole in the output breaker, and a damaged cable lug at the first point of connection. All three are found by measuring at the alternator terminals first and then moving outward, one joint at a time, rather than by removing the machine.
A genuine winding failure is the least common and the most expensive. It announces itself with a burnt smell, discoloured insulation or a resistance reading that is open or clearly different from the other two. Where a single phase has failed because of an external short, the alternator may also have damage in the same phase, so the winding check should be repeated after the external fault is cleared rather than assumed to be fine.
| Measure at | What you are testing | If it reads correctly |
|---|---|---|
| Alternator terminals, phase to phase | The winding and its internal connections | The machine is producing; the fault is downstream |
| Alternator terminals, phase to neutral | The same winding against the star point | Confirms whether one phase alone is affected |
| Output breaker, line side | The cable between alternator and breaker | Cable and lugs are sound |
| Output breaker, load side | The breaker poles | Breaker is passing all three phases |
| ATS input and output | The changeover contacts | Transfer switch is not dropping a phase |
| Distribution board incoming | The final cable run | Fault is inside the installation, not the set |
Separating the machine from the installation
Half of the no-power call-outs I hear about are not alternator faults. The machine produces, and the power stops somewhere between the terminals and the load. The only way to know is to disconnect the output at the alternator and measure there with the set running and nothing connected.
That single test splits the problem in two and cannot be skipped. If voltage appears at the alternator terminals with the output isolated, the machine is healthy and the search moves along the cable, the breaker and the transfer switch. If it does not, the machine is at fault and the installation can be left alone.
Running a set with the output isolated for a short measurement is normal practice, but it should be brief: a machine with no load and a live field will hold voltage, and there is no benefit in leaving it there while tools are collected. Measure, record, shut down.
The order that avoids replacing good parts
Every step below either eliminates a system or points at a component. None of them requires removing the alternator, and the expensive step comes last because most faults are found before it.
| Step | Action | Decides |
|---|---|---|
| 1 | Confirm engine speed is at the rated frequency | Whether this is an engine fault wearing an electrical symptom |
| 2 | Measure at the alternator terminals with output isolated | Machine or installation |
| 3 | Check the AVR supply fuse and voltage at the AVR | A dead module versus a dead supply |
| 4 | Check field resistance for continuity | Open or shorted field before any module is replaced |
| 5 | Inspect brushes and slip rings where fitted | Wear and tracking |
| 6 | Test rotating diodes in both directions | Open or shorted rectifier |
| 7 | Compare the three stator phase resistances | Winding fault versus connection fault |
| 8 | Only then consider flashing the field or replacing the AVR | The two fixes that are done last and most often wrongly |
Where this stops and a rewinding shop begins
The logic on this page is a rule of thumb for ordering checks. It deliberately does not quote resistance values, capacitances or excitation currents, because those belong to the specific alternator build and quoting a generic figure would be worse than quoting none. Get the data sheet for your machine before condemning a winding.
It also assumes the set was correctly wired at installation. A machine connected for the wrong voltage, or with the star point configured incorrectly for the site, produces readings that look like faults and are not. Where a set has never produced since installation, the connection and the voltage configuration are the first things to check, not the last.
Finally, a burned winding is not a diagnosis on its own. Windings burn because something else failed: a short circuit downstream, a lost field, a cooling failure, or an overload that the protection did not catch. Replacing the alternator without finding that cause is how the same failure happens twice.
What to send us so we can point at the right component
Send the readings rather than the conclusion. A set described as not producing power can be six different faults, and the numbers you already have usually narrow it to one before any part is ordered.
| What to send | Why it decides the answer |
|---|---|
| Alternator model and rating plate photo | The build decides which excitation system you have |
| Voltage on each phase at the terminals, with output isolated | Splits machine from installation in one reading |
| Whether the voltage collapses under load or is absent from the start | Separates weak excitation from none |
| Frequency at the same moment | Rules out an engine speed fault |
| Any history of the set standing idle, or of work on the wiring | Points at lost residual magnetism |
| Whether the AVR has already been replaced | A repeated failure points at the field, not the module |
FAQ
My generator runs but shows no voltage. Where do I start?
At the alternator terminals with the output isolated. That one reading tells you whether the machine or the installation is at fault, and everything else follows from it.
Can a generator lose its voltage just from standing idle?
Yes. A self-excited machine depends on residual magnetism in the rotor, and a long period standing can leave too little to build on. Restoring it is a stopped-machine procedure with the output isolated, done to the maker's instructions.
How do I know if the AVR is faulty?
Check its supply first: a blown fuse or a dead supply terminal gives exactly the same symptom as a failed module. Only after the supply and the field resistance are proven should the AVR be replaced.
Why is only one phase low?
Because two phases are working, so the field is fine. Look at the terminal lugs, the output breaker poles and the cable joints before suspecting the winding.
The voltage reads normal with no load but collapses when I connect the load. What is that?
Weak excitation: the AVR cannot hold voltage as current rises, or the field circuit has resistance in it. It is a different fault from no voltage at all.
Can I test the alternator with a multimeter only?
For continuity, balance between phases and diode direction, yes. For insulation resistance you need an insulation tester, and a multimeter cannot tell you whether a winding is sound at operating voltage.
Should I replace the alternator if one phase has failed?
Not before the cause is found. A phase that failed because of a downstream short will fail again in the same place if the short is still there.