Two numbers decide whether a battery starts a generator: cranking current, which is what turns the engine, and capacity, which is what keeps the controller and the charger alive when the set is off. A battery with plenty of capacity and too little cranking current will still fail on a cold morning.
Two numbers that are routinely confused
Cranking current, quoted as CCA or a regional equivalent, is the current the battery can deliver for a short burst at a specified low temperature. It is what actually turns a diesel engine against compression. Capacity in amp-hours is a different quantity: it describes how much energy the battery holds for slow discharge, which is what feeds the controller, the fuel shutoff and any standby drain.
A battery can be generous in amp-hours and marginal in cranking current. On a generator that is precisely the wrong way round, because the load is a short violent one rather than a long gentle one. It will hold a charge, read fine on a voltmeter, and still fail to spin the engine.
Cold is the condition CCA is defined at, which makes the figure look irrelevant in Nigeria. It is not: a battery aged by heat loses cranking capability in the same way a cold one does, and an old battery in a hot climate can behave like a new one in a cold one.
State of charge is readable at the terminals
A lead-acid battery left to rest for a few hours settles at an open-circuit voltage that corresponds to its state of charge. That makes a multimeter the cheapest diagnostic tool on the site, provided it is used with the charger off and the surface charge removed by a brief load.
The figures below are the ordinary lead-acid relationship. They tell you whether a battery is charged, not whether it is healthy: a tired battery can show a good resting voltage and still collapse the moment it is asked for cranking current. That is what a load test is for.
| Open-circuit voltage | Approximate state of charge | What to do |
|---|---|---|
| About 12.6 V or above | Fully charged | Nothing; record the reading for comparison |
| About 12.4 V | Roughly three quarters | Charge and re-test with the charger off |
| About 12.2 V | Roughly half | Charge before further use; investigate the charger |
| About 12.0 V | Low | Charge, then load test; suspect the charging circuit |
| Below about 11.8 V | Effectively flat | Load test; replacement is likely |
| Reads 12.6 V but collapses under cranking | Surface charge only | Load test; the battery is not holding capacity |
What keeps it charged, and what quietly stops doing so
A running engine charges through the belt-driven alternator on the set. A set that stands for long periods cannot rely on that, so it either needs a mains-powered float charger or it needs to be run often enough to matter. Many installations have both and neither is working.
The charging failures that matter are quiet ones: a slack or glazed belt, a corroded terminal that passes voltage but not current, a charger whose output has drifted, or a charger connected through a circuit that is dead when the changeover is in the other position. Each produces the same symptom, which is a battery that goes flat while everything appears normal. The changeover is the usual place to look, and the ATS panel page sets out how the control side is arranged.
Terminal condition deserves its own mention. A terminal that is tight but oxidised will read correctly on a voltmeter and still refuse to pass cranking current, which is why cleaning and re-torquing the terminals is part of the diagnosis rather than a cosmetic step.
Heat is why batteries fail early here
Lead-acid battery life falls as temperature rises, because the internal chemical reactions that shorten life run faster when the battery is warm. A battery in a plant room that sits above 35 degrees C for most of the year will not reach the life it would in a temperate installation, even if its electrical duty is identical.
That has two practical consequences. The first is that battery replacement should be planned on age and condition, not only on failure, because a battery that fails at the start of an outage costs far more than one replaced on schedule. The second is that the battery should not be mounted where the set's own heat or the exhaust runs past it.
The same heat logic applies to the rest of the machine, which is why the ambient question in high-temperature derating is not only about output. A hot plant room shortens the life of every component in it, which is the same mechanism that produces the symptoms in overheating diagnosis.
How long a parked set can stand before it will not start
There is no single number, and any page that gives one is guessing. A battery in good condition, disconnected and cool, holds charge for months. The same battery connected to a controller with a small parasitic drain, in a warm room, is a different proposition entirely, and self-discharge plus drain can flatten it in a few weeks.
The honest method is to measure rather than estimate. Read the open-circuit voltage when the set is put away, again after two weeks, and again after a month. That gives the site's own discharge curve, which is the only figure that predicts this installation. Once the curve is known the service interval for a top-up charge follows from it.
In the rainy season the case for measuring gets stronger, because lower temperatures slow self-discharge while higher humidity accelerates terminal corrosion. Neither effect is large enough to plan from a rule of thumb, and both are visible in a voltage log.
Specifying the battery and the charger
The battery should be specified from the engine's cranking requirement, not copied from whatever was fitted last time. Engine displacement, compression ratio and starting method determine the current needed, and the figure is in the engine data rather than in the generator brochure. Where it is not stated, it has to come from the factory.
The charger should be sized to the battery's capacity and should be the float type that can stay connected indefinitely without boiling the battery dry. A charger that is too large for the battery is a slow way to destroy it, and one that is too small never finishes the job. Both belong in the service schedule, which is covered in maintenance service.
For a site where the set stands for long periods, a small solar maintainer can be a better answer than a mains charger, provided it is regulated. If the set is hard to start in the first place, the fault may not be the battery at all, and will not start diagnosis is the right next step.
FAQ
How often should a generator battery be replaced in Nigeria?
Plan on condition and age rather than a fixed interval, because heat shortens life and the plant room temperature varies by site. A battery that passes a load test and holds charge can stay; one that fails a load test should be replaced before it fails during an outage.
Why does my generator battery go flat when the set is not used?
Either the battery is no longer holding charge, or something is draining it: a controller standby load, a faulty charger, or a charger fed from a circuit that is dead when the changeover is on the other source. A voltage log over a few weeks separates those.
Can I use a car battery to start a generator?
Only if its cranking current meets the engine's requirement. Capacity in amp-hours is not the deciding figure, and a car battery chosen on size rather than cranking current is a common reason a set cranks slowly.
Does the battery need a charger if the set runs daily?
Usually not, if the belt-driven alternator is healthy and the runs are long enough to replace what the start consumed. Sets that run briefly and often benefit from a float charger because short runs do not put back what starting took out.
What voltage should a healthy 12 V generator battery show?
About 12.6 V or slightly above at rest, with the charger off and the surface charge removed. That figure indicates charge, not health; a battery can show it and still fail under cranking load.