A generator only delivers its nameplate kVA at the ambient and altitude its rating was defined at. Run it at 40 degrees C instead, and the usable figure comes off the manufacturer's derating curve, which for a nominal 100 kVA set commonly lands in the high 80s or around 90 kVA.
The nameplate is a laboratory figure, not a site figure
Every generator rating is defined against a set of reference conditions. Those conditions usually include an ambient air temperature, an altitude, a power factor, a duty class and a cooling arrangement. The badge on the set does not repeat them, but they are always there, and they are what makes a 100 kVA figure mean one thing on a datasheet and something slightly smaller in a plant room in Lagos.
This matters more in Nigeria than in a temperate market, because the reference ambient on a general-purpose data sheet is often cooler than the air the set will actually breathe. Two sets with the same badge and different reference ambients are not the same machine on site: the one specified for a hot climate holds its figure at a higher temperature, and the one specified for a mild climate does not.
So the first useful question about any set is not how many kVA it is, but at what ambient that number was defined. If a supplier cannot answer that, the badge is not yet a specification. The sizing guide covers the load side of this problem; this page covers the capacity side.
What 40 degrees C ambient does to a nominal 100 kVA set
Heat attacks the rating from two directions at once. The alternator is limited by how much temperature rise its insulation can tolerate above the surrounding air, so a hotter room leaves less headroom for the same electrical output. The engine side is limited by the radiator, which rejects heat into the air at a rate that depends on the difference between the coolant and the ambient. Raise the ambient and that difference shrinks, so the same radiator cannot carry away the same heat.
That is why the loss is not a small correction. A set whose rating was defined at a cooler reference ambient, then installed where the air sits at 40 degrees C for hours at a time, does not produce its badge figure. In the common case a nominal 100 kVA unit lands in the high 80s or around 90 kVA of usable output, and the exact figure belongs to that model's curve rather than to this page.
The practical consequence is a set that appears to be correctly sized on paper and then trips, derates its own output, or runs hot the first time the site reaches full demand on a still afternoon. Nothing is broken; the site simply asked for the nameplate number rather than the site number.
Altitude is the second derating that rarely gets quoted
Air gets thinner with height, and a diesel engine is an air pump. Less dense air means less oxygen per stroke, so the fuel that can be burned cleanly per cycle falls with it. At the same time the radiator has less mass of cooling air to work with, which compounds the thermal side of the same problem.
The rule used across the industry is roughly one per cent of output for every 100 m above about 1,000 m, with the derating starting at the threshold rather than at sea level. Lagos sits at sea level, so altitude is not the issue on the coast and the 40 degrees C ambient is the whole story there. Inland it is a different picture: parts of the plateau sit above the 1,000 m threshold, and a site at that height carries an altitude deduction on top of the temperature one.
For most coastal and mid-belt installations the honest answer is that altitude contributes nothing and temperature contributes everything. The mistake is assuming that holds for the whole country, and sizing an inland site from a coastal reference.
Reading the curve, and the arithmetic behind the number
The working method is a chain of multipliers, each taken from a curve rather than guessed: usable output equals nameplate output multiplied by the temperature factor, then by the altitude factor, then checked against the duty rating that applies to how the set will actually run. Each factor is read at the site's own condition, not at an average.
As an illustration only, if a curve gives a temperature factor of 0.89 at the site ambient and the altitude is below the threshold, a nominal 100 kVA set works out at 89 kVA. The arithmetic is trivial; the discipline is refusing to use a factor that came from a different model, a different cooling package or a different reference ambient. That is the part a factory can answer and a brochure cannot.
The table is a map of which condition changes what, so that the right curve is consulted for the right reason.
| Site condition | What it changes | Where the allowance comes from |
|---|---|---|
| Sea level, the reference ambient on the data sheet | Nothing. This is what the nameplate means | The data sheet itself; no correction applies |
| Sea level, 40 degrees C ambient | Alternator temperature rise and radiator heat rejection both tighten | The temperature derating curve for that model |
| Above roughly 1,000 m | Less oxygen per stroke, and thinner cooling air | The altitude curve, or about one per cent per 100 m above the threshold |
| Enclosed canopy or plant room with poor air flow | The set breathes its own hot discharge air | Not a rating allowance: fix the installation, not the badge |
| Continuous duty rather than standby | A lower rating applies to the same machine | The duty definitions on the data sheet |
| Radiator core blocked with dust or debris | Heat rejection falls below the design figure | Maintenance, not derating; clean the core |
How much headroom to specify, without guessing
Headroom is not a fixed percentage added at the end. The order that works is to establish the site's real maximum demand including the largest motor start, divide that by the derating factors for the site conditions, and then check the result against the continuous rating rather than the standby rating. The figure that comes out is the one to price.
Adding a flat margin on top of an already derated figure double counts. It also pushes the set into a light-load condition for most of its life, which carries its own cost: a set run well below its rating does not reach clean combustion temperatures, and the consequences of that are set out in under-loading damage.
A better question than how much margin to add is what the worst hour of the year looks like. If the site reaches its peak on the hottest still afternoon with every air conditioner running, that hour sets the rating. If the peak arrives at night with a light load, the derating is gentler and the set can be smaller. Sizing to the average is how sites end up short at the worst moment. The conversion between kilowatts and kilovolt-amperes, and the difference between a rating and an energy figure, is set out in kW, kVA and kWh.
What to ask before the rating is fixed
Four questions settle most of it. At what ambient is this rating defined. At what altitude. What is the continuous rating as distinct from the standby rating. And can I see the derating curve for this model rather than a general statement that it is tropicalised.
A supplier who answers those in writing has given you something you can check against the site. One who answers with an adjective has not. The same discipline applies to the cooling side of the machine, which is where most hot-climate failures actually start; the checks in overheating diagnosis are the ones to run if a derated set still runs hot after installation.
If the site also has a large motor load, the starting current rather than the running load may decide the rating, and that interaction is covered in three-phase motor sizing. Derating and motor starting are two separate deductions, and a set can be defeated by either.
FAQ
Is a 100 kVA generator still 100 kVA in Lagos?
Only if the rating was defined at the ambient the site actually sees. Where the site runs hotter than the reference ambient on the data sheet, the usable figure is the curve value at that temperature, and for a nominal 100 kVA set that commonly lands in the high 80s or around 90 kVA.
Does altitude matter anywhere in Nigeria?
At the coast it does not. Inland it can: the usual rule is about one per cent per 100 m above roughly 1,000 m, and parts of the plateau sit above that threshold, so those sites carry an altitude deduction on top of the temperature one.
Can I recover the lost output by opening the canopy doors?
That can help a set that is recirculating its own hot air, which is an installation fault rather than a rating one. It does not change what the set is rated to produce at that ambient, and it is not a substitute for sizing on the derated figure.
Does a larger radiator solve the problem?
A cooling package specified for a higher ambient raises the temperature at which the rating holds, which is the legitimate way to buy back capacity. It has to come with the alternator and engine rating that match it, otherwise the radiator is no longer the limiting item.
Should I simply buy one size up?
Not blindly. Sizing one step up can land the set in a healthy band or push it into permanent light load, depending on the real demand. Derate first, then check where the result sits in the load band.