Handover is not a demonstration. It is a transfer of three things: the ability to start, load and stop the set correctly, a written daily check with limits, and an agreed list of who may open what. If the site cannot answer those three questions a week later, the handover did not happen.
What a handover should transfer
A generator is delivered to a building, not to a person. The people who receive it are usually security staff, a facility supervisor and an electrician, and none of them was in the conversation that decided the rating, the enclosure or the changeover arrangement. Handover is the process that closes that gap, and it has to be deliberate because nothing else in the transaction carries the information across.
Three things need to move. The first is procedural knowledge: how to start the set, how to put load on it, how to stop it, and what to do when an alarm appears. The second is a written routine: a daily check with pass limits, so that a person who was not trained can still notice that something has changed. The third is authority: a clear answer to who may open the canopy, who may reset an alarm, and who must be called instead.
What does not need to move is everything the supplier knows about engines. An operator does not need to understand injection timing to run a set well; they need to know that a knocking sound means stop, that the oil pressure gauge should sit in a particular place when hot, and that the set must not be run at a small fraction of its rating for days on end. Training that starts from theory and ends without those three facts has failed.
The timing matters too. Handover should happen after commissioning and after the break-in ladder has begun, so the readings the operator is taught to expect are the readings the machine is actually giving. A handover conducted before the set has run under load teaches numbers that will change within a week. The break-in schedule sets out what the first fifty hours should look like, and the operator should be walked through it rather than told about it.
The training walk-through
A walk-through that works takes about two hours and follows the machine rather than a syllabus. It starts outside the canopy, because that is where the operator will stand, and it ends with the operator starting the set unaided while the trainer watches without intervening.
Outside first. Point out the air inlet and outlet, explain why nothing may be stacked against them, and show where the exhaust discharges. Show the fuel fill point and the bund, and explain that the tank is filled to a level rather than to the brim. Show the earth connection and the reason it exists, which the earthing and grounding guide covers for the technical reader.
Then the canopy interior. Identify the dipstick, the coolant cap, the air filter housing, the fuel filter and the water trap, and say plainly which of them may be touched by an operator and which may not. Show the battery and its isolator. Open the control panel and go through every indication on it: what each gauge reads when the set is healthy, what each alarm means, and which alarms require a stop.
Then the sequence. Trainer starts the set, explaining each step aloud. Then the operator starts it with the trainer talking them through. Then the operator starts it in silence, and the trainer says nothing at all, including when a step is done in the wrong order. The silence is the part that reveals whether the knowledge transferred.
Then the load. Put load on in steps, and show how the frequency and voltage move as each step arrives. Explain the difference between a dip that recovers and a dip that persists, because that distinction is the one that tells an operator whether to keep going or to stop. The kVA to kW and amps chart is the reference for what the current readings should be at each rating.
Then the stop. Stop with load removed first, then cool-down, then the isolator. Explain why the set should not be stopped abruptly under load, and why it should not be left idling for long periods afterwards.
The daily check sheet
The check sheet is the part of the handover that keeps working after the trainer leaves. It should be short enough to be done honestly every day, and specific enough that a wrong reading is obvious rather than a matter of opinion. Ten items and a place to write the date and the hours are enough.
| Check | How | Pass | If it fails |
|---|---|---|---|
| Engine oil level | Dipstick, engine stopped and level | Between the marks | Top up with the specified grade and note the amount |
| Coolant level | Header tank, engine cold | At the mark | Do not open a hot cap; find the leak before running |
| Fuel level | Tank gauge or dip | Above a quarter | Refuel before starting, never during a run |
| Water trap | Drain a little into a clear jar | Clean fuel, no water line | Drain until clear and investigate the source |
| Air inlet | Visual, both sides | Clear, no nesting, no dust cake | Clear the obstruction, replace the element if loaded |
| Battery | Terminals and charger indication | Clean and tight, charger showing charge | Clean and tighten, test before the next start |
| Leaks | Look under the set | Dry | Identify the fluid; do not run on a fuel or coolant leak |
| Exhaust at load | Observe after load is applied | Light haze at most | Stop if black or blue persists |
| Noise and vibration | Listen at the panel for a minute | Steady, familiar | Stop on any new knock or heavy vibration |
| Hour meter | Read and record | Increasing as expected | Investigate a meter that does not move |
The sheet is also the record that makes a warranty conversation possible later, because it shows what the site observed and when. A blank sheet and a failed engine is a hard position; a dated sheet showing a coolant loss logged three days before the failure is a different conversation. The warranty and after-sales guide explains what else belongs in that file.
Keep it on a clipboard at the set, not in an office. A sheet that has to be fetched is a sheet that gets filled in from memory at the end of the week, which defeats the purpose entirely.
The documents to leave behind
A handover pack should fit in one folder and be usable by someone who was not at the training. Six documents cover it: the engine and alternator manuals, the controller manual, the wiring diagram for the installation as built, the commissioning and test record, and the completed daily check sheet with the first entries already written.
The wiring diagram is the one most often missing, because the installation was done from a standard drawing that was never marked up. An as-built diagram showing which breaker feeds what, where the changeover sits and how the neutral and earth are arranged is worth more than a shelf of catalogues. Without it, the next electrician rediscovers the installation by testing it live.
Add a one-page summary written by the person who did the handover, in plain language: the rating, the duty, the fuel capacity, the oil grade, the service interval, the name and number of the person to call, and the three things that must never be done. That page is what gets read at two in the morning when something has stopped.
Where the site has more than one operator, keep a signed attendance sheet from the training. It is not bureaucracy; it identifies who was actually taught, which matters when a shift pattern changes and a set fails in a way that suggests nobody was.
Misoperations that recur
The same mistakes appear across sites of every size, and most of them come from a reasonable instinct applied to the wrong machine.
Running light to be kind. An operator who keeps the load low because the set sounds happier at no load is glazing the bores. Diesel engines want load; the under-loading guide explains the mechanism and what it costs.
Resetting instead of diagnosing. A panel that restarts after a shutdown is convenient, and convenience trains people to reset first and look afterwards. The habit usually ends with a set that will not start at all.
Topping up coolant on a hot engine. The cap comes off under pressure and the operator is scalded, and the cold coolant cracked into a hot block can crack the block itself. This is worth demonstrating rather than describing.
Filling fuel while running. A spill onto a hot exhaust is a fire, and the practice also lets dirt into the tank. The fuel storage guide covers filtration and settling, which is where fuel quality is actually decided.
Jump-starting from a running vehicle. The surge can damage the controller, and on a set with an electronic panel the replacement is neither quick nor cheap. The battery and starting guide covers charging and replacement instead.
Ignoring a new noise. Operators hear the set every day and are the best sensor on the site, but only if reporting a noise is normal rather than an admission of fault. Say so explicitly during training.
The first month
The month after handover is when the arrangement is tested. Two things make the difference between a site that settles into a routine and one that drifts back to improvisation.
The first is a short review at the end of the first week, with the check sheet in hand. Look for entries that are repeated, entries that are blank, and entries written in the same handwriting for several days, which usually means they were filled in retrospectively. Correcting that in week one is easy; correcting it in month six is not.
The second is a clear route for questions. An operator who has been told to call a number and gets no answer will stop calling, and the next event will be a failure rather than a question. Agree the route during handover, test it once during the first week, and keep the same number in the handover pack.
After the first service interval the set moves onto the normal maintenance ladder and the handover is effectively complete. The maintenance schedule sets out the intervals from that point, and the generator range pages give the ratings and engine options that the schedule is written against.
Handover questions
What should a generator handover include?
Three things: a practical walk-through that ends with the operator starting the set unaided, a written daily check sheet with pass limits, and an agreed list of who may reset alarms and open the canopy.
How long does operator training take?
About two hours for a walk-through that covers the outside of the set, the canopy interior, the start and stop sequence, and load steps. The useful test is whether the operator can repeat it in silence afterwards.
Which alarms may an operator reset?
A short listed set, typically a low fuel shutdown, an over-crank and a high temperature that has since cooled. Anything indicating low oil pressure, over-speed or an electrical fault should go to the electrician or the supplier rather than being reset.
What is the most common operator mistake?
Running the set at light load because it sounds smoother. A diesel that never carries load glazes its bores, and the damage is done before anyone notices a symptom.
What records should the site keep?
The daily check sheet with dates and hours, the commissioning and test record, the as-built wiring diagram and the service history. Those four answer almost every warranty or diagnosis question that arises later.
Do we need a dedicated operator?
Not necessarily, but the site needs a named person who is accountable for the checks and a named person to call. A set shared by everyone with no name against it is the arrangement that fails.
Get a written quotation
Three fields. We reply with the rating, the engine option and the delivery basis.