Running cost equals fuel consumption per hour multiplied by the local diesel price. Because diesel prices vary between cities and change from week to week, any cost figure has to state the price and the date it was taken.
The calculation in three steps
The method has three parts. First, express the load in kW. Second, apply a consumption rate per kWh to get litres per hour. Third, multiply by the diesel price to get a running cost.
For the second step, an industry rule of thumb for diesel generators is about 0.21 to 0.25 litres per kWh at full load. Applying that rate to a 10 kW set running at full load gives roughly 2.1 to 2.5 litres per hour. The rule is a planning aid; the datasheet figure for the specific engine model is what should be used for a firm estimate.
The third step is where most estimates go wrong. Because diesel prices differ between cities and move over time, a cost figure without a stated price and date cannot be compared with anything. State both.
Why part load costs more per unit
Fuel consumption does not fall in proportion to load. A set running at half its rating consumes more than half the fuel it would use at full output, so the litres required for each kWh delivered rise as the load falls.
The practical consequence is that a heavily oversized generator can cost more to run than a correctly sized one, even though both do the same job. The saving from a smaller, well-matched set appears on the fuel bill rather than on the invoice.
This is also the argument for load management. Where a site can keep its load in a band rather than swinging between very light and very heavy, the specific consumption stays closer to the efficient range.
The kW, kVA and kWh guide explains the units used in these steps, and the fuel consumption calculator applies them to your own figures.
Every cost estimate multiplies litres by a price, and that price is the least stable input; see what moves the Lagos diesel price.
Runtime and energy delivered
Energy delivered is power multiplied by time, so a set running at 40 kW for five hours delivers 200 kWh. That figure is the one that matters for fuel and cost rather than the instantaneous rating.
Stating the requirement in hours of runtime at the expected load is also the clearest way to describe fuel autonomy for a site. Runtime equals stored fuel divided by consumption at that load, so the runtime target drives the tank arrangement rather than the other way around.
For sites that run to a schedule rather than continuously, it is worth calculating both a daily and a monthly figure. The monthly figure is usually the one that matters commercially, and it is the one that justifies action if consumption is higher than expected.
The 10kW fuel consumption guide works through a smaller set, and the 10kW buying guide covers the selection side.
Options that reduce consumption without a compromise
The most effective lever is sizing. A set matched to the real load spends more of its time in an efficient band than an oversized one, and that difference compounds over a year of operation.
The second lever is how the load is managed. Sequencing heavy starts and avoiding long periods at very light load both keep the set closer to its efficient range.
The third is maintenance. Filters, fuel quality and injector condition all affect consumption, which is why the service interval belongs in the operating calculation rather than being treated as a separate concern. The spare parts guide covers the consumables involved.
Estimating a figure by hand is covered here; the same calculation as an interactive tool is at the diesel consumption calculator.
Getting a figure you can rely on
Send the load list or rating, the expected average load as a percentage of the rating, the daily and monthly hours of use, and your local diesel price with the date it was taken. Ask for the consumption figure for the offered engine model on its datasheet, since a planning rule is not a substitute for the machine's own data.
Request a consumption estimate
Send the load or rating, the expected average load, the hours of use and your local diesel price with its date, and ask for the datasheet consumption figure for the offered engine model.
Get a written quotation
Three fields. We reply with the rating, the engine option and the delivery basis.
Fuel consumption questions
How much fuel does a diesel generator use per kWh?
As an industry rule of thumb, about 0.21 to 0.25 litres per kWh at full load. The datasheet figure for the specific engine model should be used where a firm estimate is needed.
How much fuel does a 10 kW set use per hour?
Applying the planning rule at full load gives roughly 2.1 to 2.5 litres per hour. Consumption at part load rises per kWh, so the figure depends on how heavily the set is loaded.
Does running a generator at part load save fuel?
Not in proportion. Fuel use falls less than load does, so the litres required for each kWh delivered rise as load falls. A heavily oversized set can cost more to run than a correctly matched one.
How do I calculate running cost?
Fuel consumption per hour multiplied by the local diesel price. Because prices differ between cities and change weekly, any cost figure must state the price and the date used.
What is the best way to describe fuel autonomy?
In hours of runtime at the expected load rather than in litres, because runtime equals stored fuel divided by consumption at that load. The runtime target then drives the tank arrangement.
What else affects consumption?
Load management and maintenance. Keeping heavy starts sequenced, avoiding long periods at very light load, and looking after filters, fuel quality and injectors all influence the litres-per-kWh figure in practice.